What is the output range of the AS-BDAU-208?
It provides ±10 V analog outputs across 8 channels.
1 actual photo shown first. Reference images are model-matched and must be confirmed before purchase.
Schneider Electric
AS-BDAU-208
Schneider Electric
The AS-BDAU-208 is an 8-channel analog output module for Modicon PLC systems, engineered to deliver precise ±10 V outputs across multiple control points. It provides 11-bit resolution with sign and ±0.1% of full-scale accuracy, enabling dependable voltage control in demanding industrial environments. The module supports fast conversion of under 1 ms for all channels and requires loads greater than 3.3 kΩ. Electrical isolation is rated at 700 V for channel-to-bus and channel-to-external supply, with no isolation channel-to-channel. Internal power requirements are ≤30 mA at 5 V, and external power requirements are ≤120 mA at 24 VDC. Typical certifications include UL, cUL, FM, and CE, supporting compliance in regulated applications. This unit integrates within Schneider Electric Modicon architectures and is suitable for applications needing stable analog voltage output and robust isolation. Package weight is listed variably by sources and should be verified for specific installations.
Actual photos when available
Nameplate, condition, and visible wear can be shared before quote when stock photos are not enough.
Test notes for used units
Power-on or function test status is stated when available, with clear condition grading.
Trackable global shipping
DHL, FedEx, UPS, or forwarder options can be quoted with packing photos and tracking details.
Clear DOA boundary
For tested units, quote terms can include 7-day DOA support unless otherwise stated.
Independent sourcing disclaimer
We are not an authorized distributor, reseller, or representative of Siemens, Mitsubishi, Omron, or other manufacturers listed on this site. All product names, trademarks, brands, and logos are the property of their respective owners. Products may be used, refurbished, surplus, or sourced from the secondary market unless otherwise stated.
Prices and stock can change. Submit quantity, required condition, and destination for a current quote.
It provides ±10 V analog outputs across 8 channels.
11-bit resolution with sign for precise voltage control.
No channel-to-channel isolation; isolation is 700 V to bus and external supply.
Greater than 3.3 kΩ per output channel.
≤30 mA at 5 V internally and ≤120 mA at 24 VDC externally.