UsedAutomations — TESTED SURPLUS & OBSOLETE CONTROLS

1 actual photo shown first. Reference images are model-matched and must be confirmed before purchase.

Schneider Electric

140-ACI-040-00

Analog Input Module, 16‑Channel Differential, 4–20 mA

Schneider Electric

From $990In stockDiscontinued

Product Description

This analog input module delivers 16 differential channels for 4–20 mA signal acquisition, suited for distributed I/O in industrial automation systems. It employs a single‑pole low‑pass filter with a 3 dB cutoff around 34 Hz to reduce noise while maintaining signal fidelity. The module provides 12‑bit resolution (0 to 4095 counts) for current inputs and includes broken‑wire detection for 4–20 mA loops to improve diagnostics. Isolation between channels and the backplane bus is rated to withstand 1780 VAC for 60 seconds, enhancing safety and noise immunity. Local signaling is provided via per‑channel LEDs to indicate fault status for rapid troubleshooting. Power consumption is optimized with a 5 W dissipation and a 360 mA bus current requirement. Typical applications include process instrumentation, manufacturing cells, and monitoring systems where reliable analog data capture and robust EMC performance are required. The module follows standard format for easy integration and addressing requires 17 input words.

Key Features

  • 16 differential analog input channels
  • 4–20 mA inputs, 12‑bit resolution
  • Single‑pole low‑pass filter around 34 Hz
  • Broken wire detection on 4–20 mA loops
  • 1780 VAC isolation channel to bus
  • Per‑channel LED fault indication
  • 5 W power dissipation, 360 mA bus current

Specifications

Model number
140-ACI-040-00
Input channels
16 differential
Input signal
4–20 mA
Resolution
0–4095 counts
Filter
Single pole low pass, 3 dB at 34 Hz ±25%
Isolation (channel to bus)
1780 VAC for 60 s
Bus current requirement
360 mA
Power dissipation
5 W
Input impedance
250 Ω
Absolute maximum input
30 mA
Common mode rejection
> −90 dB at 60 Hz
Addressing
17 input words
Fault detection
Broken wire 4–20 mA
Local signaling
16 red LEDs channel fault
Marking
CE
Module format
Standard

Before we quote this part

Actual photos when available

Nameplate, condition, and visible wear can be shared before quote when stock photos are not enough.

Test notes for used units

Power-on or function test status is stated when available, with clear condition grading.

Trackable global shipping

DHL, FedEx, UPS, or forwarder options can be quoted with packing photos and tracking details.

Clear DOA boundary

For tested units, quote terms can include 7-day DOA support unless otherwise stated.

Independent sourcing disclaimer

We are not an authorized distributor, reseller, or representative of Siemens, Mitsubishi, Omron, or other manufacturers listed on this site. All product names, trademarks, brands, and logos are the property of their respective owners. Products may be used, refurbished, surplus, or sourced from the secondary market unless otherwise stated.

Need 140-ACI-040-00 availability?

Prices and stock can change. Submit quantity, required condition, and destination for a current quote.

Request Quote

FAQ

What types of signals does this module accept?

Differential 4–20 mA analog inputs across 16 channels

What is the input resolution?

12‑bit resolution providing 0–4095 counts for 4–20 mA

Is there isolation between I/O and the bus?

Yes, 1780 VAC isolation for 60 seconds channel to bus

Does it detect loop faults?

Yes, broken wire detection for 4–20 mA loops with LED indication

What are the power requirements?

360 mA bus current with 5 W power dissipation