The QX82 is a 64-point DC input module for Mitsubishi MELSEC-Q (QnU) PLC systems designed for high-density digital input acquisition. It accepts 24 VDC sourcing inputs and uses photocoupler isolation to protect the backplane and adjacent modules from field transients. Default input response is 10 ms with configurable filtering from 1 to 70 ms via PLC parameters, enabling noise immunity and deterministic scan behavior based on application needs. The module employs a negative common arrangement with 32 points per common and presents approximately 5.6 kΩ input impedance. Electrical thresholds are specified at 19 V/3 mA minimum for ON and 11 V/1.7 mA maximum for OFF, supporting robust detection under industrial conditions. It withstands 560 VAC rms across insulation for three cycles at altitudes up to 2000 m and meets insulation resistance of 10 MΩ or greater. This unit integrates into the Q series backplane and interfaces via A6CON style connectors in typical deployments. It is suited for machine I/O concentration, panel space optimization, and applications requiring reliable 24 VDC input sensing across large point counts.

Key Features

  • 64-point 24 VDC digital input density
  • Configurable input filter 1 to 70 ms
  • Photocoupler isolated input channels
  • Negative common type, 32 points per common
  • ON threshold ≥19 V and ≥3 mA
  • OFF threshold ≤11 V and ≤1.7 mA
  • Approx. 5.6 kΩ input impedance

Buy Options

Condition, indicative price, stock, and lead time. Confirm current availability via RFQ.

New

Price: $711.58
Availability: 1 in stock
Lead time: ~10 day lead

Never Used

Price: $618.52
Availability: 2 in stock
Lead time: ~6 day lead

Used

Price: $235.94
Availability: 67 in stock
Lead time: ~2 day lead

FNFP

Price: $978
Availability: 3 in stock
Lead time: ~2 day lead

Specifications

Brand
MITSUBISHI
Model
QX82
Module Type
DC input module, negative common
Input Points
64 points
Rated Input Voltage
24 VDC (+20/−15%), ripple ≤5%
Rated Input Current
Approx. 4 mA
ON Voltage / Current
≥19 V / ≥3 mA
OFF Voltage / Current
≤11 V / ≤1.7 mA
Input Impedance
Approx. 5.6 kΩ
Isolation Method
Photocoupler
Response Time (ON/OFF)
1/5/10/20/70 ms or less, default 10 ms (set in PLC parameters)
Common Arrangement
32 points per common (terminals 1B01, 1B02, 2B01, 2B02)
Dielectric Withstand Voltage
560 VAC rms / 3 cycles (altitude ≤2000 m)
Insulation Resistance
≥10 MΩ by insulation tester
Series / Family
MELSEC-Q (QnU) series
Weight
0.56 lb (0.26 kg)
Part #
QX82
Category
PLCs/Machine Control
Category
PLC Module/Rack
Weight
0.25 lbs

Before we quote this part

Actual photos when available

Nameplate, condition, and visible wear can be shared before quote when stock photos are not enough.

Test notes for used units

Power-on or function test status is stated when available, with clear condition grading.

Trackable global shipping

DHL, FedEx, UPS, or forwarder options can be quoted with packing photos and tracking details.

Clear DOA boundary

For tested units, quote terms can include 7-day DOA support unless otherwise stated.

Independent sourcing disclaimer

We are not an authorized distributor, reseller, or representative of Siemens, Mitsubishi, Omron, or other manufacturers listed on this site. All product names, trademarks, brands, and logos are the property of their respective owners. Products may be used, refurbished, surplus, or sourced from the secondary market unless otherwise stated.

Need QX82 availability?

Prices and stock can change. Submit quantity, required condition, and destination for a current quote.

Request Quote

FAQ

Is the QX82 a sourcing or sinking input module?

It is a DC input module with negative common type, intended for 24 VDC sourcing field devices

Can the input response time be adjusted?

Yes, filtering can be set to 1, 5, 10, 20, or 70 ms in PLC parameters, default 10 ms

What isolation method is used?

Each input uses photocoupler isolation for electrical separation

How many inputs share a common?

The module has 32 points per common across designated common terminals

What are the ON/OFF threshold levels?

ON is ≥19 V and ≥3 mA; OFF is ≤11 V and ≤1.7 mA at 24 VDC