What is the interrupting rating?
14 kA at 277 VAC and 10 kA at 125 VDC
1 actual photo shown first. Reference images are model-matched and must be confirmed before purchase.
GE
TED113020
GE
This is a Type TED thermal magnetic molded case circuit breaker designed for single‑pole applications with a 20 A rating. It supports 277 VAC and 125 VDC systems, delivering interrupting capability of 14 kA at 277 VAC and 10 kA at 125 VDC. The unit features long‑time and instantaneous trip (LI) characteristics and is intended for bolt‑on mounting with load side lug terminals. The breaker is built on a 150 A frame and uses Cu/Al line and load lugs, with a calibrated 40 °C temperature rating. Typical wiring accommodates 14–8 AWG conductors, and dimensions are approximately 6.31 in H x 1.38 in W x 3.38 in D. Suitable for GE panelboards and HACR applications, it carries UL and CSA approvals. Use where reliable thermal magnetic protection, compact footprint, and straightforward bolt‑on installation are required.
Condition, indicative price, stock, and lead time. Confirm current availability via RFQ.
New
Never Used
Used
FNFP
Actual photos when available
Nameplate, condition, and visible wear can be shared before quote when stock photos are not enough.
Test notes for used units
Power-on or function test status is stated when available, with clear condition grading.
Trackable global shipping
DHL, FedEx, UPS, or forwarder options can be quoted with packing photos and tracking details.
Clear DOA boundary
For tested units, quote terms can include 7-day DOA support unless otherwise stated.
Independent sourcing disclaimer
We are not an authorized distributor, reseller, or representative of Siemens, Mitsubishi, Omron, or other manufacturers listed on this site. All product names, trademarks, brands, and logos are the property of their respective owners. Products may be used, refurbished, surplus, or sourced from the secondary market unless otherwise stated.
Prices and stock can change. Submit quantity, required condition, and destination for a current quote.
14 kA at 277 VAC and 10 kA at 125 VDC
Thermal magnetic with long‑time and instantaneous (LI)
Bolt‑on to compatible GE panelboards
14 to 8 AWG with Cu/Al lugs
Yes, UL E11592 and CSA LR57114 with HACR rating
Approximately 6.31 H x 1.38 W x 3.38 D in