What is the output voltage range?
The module provides bipolar output from −10 to +10 VDC across each channel.
1 actual photo shown first. Reference images are model-matched and must be confirmed before purchase.
Fanuc
IC693ALG390
Fanuc
The IC693ALG390 is a 2‑channel analog voltage output module for Series 90‑30 PLC systems, providing precision conversion of 13‑bit digital data to bipolar analog voltages from −10 to +10 VDC. It can be powered from the isolated +24 VDC backplane supply or a user‑supplied external source via front terminals, enabling hold‑last‑state behavior when configured appropriately. The module is factory calibrated with 2.5 mV per count resolution and delivers a typical update rate of 5 ms across both channels. Optical isolation separates field wiring from the backplane to mitigate noise coupling, and careful use of twisted, shielded instrumentation cable is recommended to minimize noise and capacitive loading. Rated maximum output load is 5 mA, with typical accuracy ±5 mV at 25 °C. External supply voltage range is 18 to 30 VDC with 10% ripple tolerance. Internal consumption is 32 mA from 5 V and 120 mA from 24 V supplies. The unit fits any I/O slot in 5‑ or 10‑slot baseplates within the Series 90‑30 family.
Actual photos when available
Nameplate, condition, and visible wear can be shared before quote when stock photos are not enough.
Test notes for used units
Power-on or function test status is stated when available, with clear condition grading.
Trackable global shipping
DHL, FedEx, UPS, or forwarder options can be quoted with packing photos and tracking details.
Clear DOA boundary
For tested units, quote terms can include 7-day DOA support unless otherwise stated.
Independent sourcing disclaimer
We are not an authorized distributor, reseller, or representative of Siemens, Mitsubishi, Omron, or other manufacturers listed on this site. All product names, trademarks, brands, and logos are the property of their respective owners. Products may be used, refurbished, surplus, or sourced from the secondary market unless otherwise stated.
Prices and stock can change. Submit quantity, required condition, and destination for a current quote.
The module provides bipolar output from −10 to +10 VDC across each channel.
Two isolated analog voltage output channels are provided.
It can use the isolated +24 VDC backplane supply or a user‑supplied external 18–30 VDC source.
Resolution is 2.5 mV per count with ±5 mV absolute accuracy at 25 °C.
Yes, it provides 1500 V RMS isolation between field wiring and the logic side.