Q: How many outputs does this module provide?
A: It provides 32 discrete DC outputs arranged in two groups of 16.
1 actual photo shown first. Reference images are model-matched and must be confirmed before purchase.
Fanuc
IC200MDL744
Fanuc
This discrete output module is designed for GE VersaMax systems and provides 32 DC outputs organized in two groups. It supports negative logic (sinking) operation with selectable modes: TTL at nominal 5 VDC and a 12/24 VDC mode with wide output ranges to accommodate various field devices. The module requires an IC200CHS series carrier base for installation and draws 140 mA from the 5 V backplane. Group-to-group isolation is rated for 250 VAC continuous and 1500 VAC for one minute, while individual point isolation is not provided. Each output includes a status LED, with additional OK and field power LEDs to aid diagnostics. There are no internal fuses, and supplemental field power is needed for load switching. This unit is suited for high-density discrete output applications where flexible DC levels and robust isolation between groups are important.
Condition, indicative price, stock, and lead time. Confirm current availability via RFQ.
New
Never Used
Used
FNFP
Actual photos when available
Nameplate, condition, and visible wear can be shared before quote when stock photos are not enough.
Test notes for used units
Power-on or function test status is stated when available, with clear condition grading.
Trackable global shipping
DHL, FedEx, UPS, or forwarder options can be quoted with packing photos and tracking details.
Clear DOA boundary
For tested units, quote terms can include 7-day DOA support unless otherwise stated.
Independent sourcing disclaimer
We are not an authorized distributor, reseller, or representative of Siemens, Mitsubishi, Omron, or other manufacturers listed on this site. All product names, trademarks, brands, and logos are the property of their respective owners. Products may be used, refurbished, surplus, or sourced from the secondary market unless otherwise stated.
Prices and stock can change. Submit quantity, required condition, and destination for a current quote.
A: It provides 32 discrete DC outputs arranged in two groups of 16.
A: TTL mode at nominal 5 VDC and a 12/24 VDC mode spanning 10.2–30 VDC.
A: There is group-to-group isolation, but no individual point isolation.
A: An IC200CHS series carrier base is required for installation.
A: No, it has no internal fuses; use external protection as needed.