What is the output voltage range?
0 to 10.24 VDC across four single-ended channels
1 actual photo shown first. Reference images are model-matched and must be confirmed before purchase.
Fanuc
IC200ALG321
Fanuc
The IC200ALG321 is a four-channel analog voltage output module designed for VersaMax systems. It provides single-ended outputs grouped in one block, delivering a 0 to 10.24 VDC range suitable for driving resistive loads down to 5 kΩ and capacitive loads up to 1.0 µF. The module features a fast 0.3 ms update rate and two status LEDs (FLD PWR, OK) for at-a-glance diagnostics. External user power is required, with a recommended supply including ripple of +18 to +30 VDC; the module draws 50 mA from the +5 V backplane. A jumper-selectable behavior allows outputs to either hold last state or default to 0 V if backplane power or communications are interrupted, provided user-side power remains. For optimal signal integrity, shielded twisted pair cabling is recommended, and shields may be terminated at terminal-style I/O carriers per field wiring guidelines. This module integrates simply within VersaMax I/O carriers and is suitable for precision voltage output applications in industrial control.
Actual photos when available
Nameplate, condition, and visible wear can be shared before quote when stock photos are not enough.
Test notes for used units
Power-on or function test status is stated when available, with clear condition grading.
Trackable global shipping
DHL, FedEx, UPS, or forwarder options can be quoted with packing photos and tracking details.
Clear DOA boundary
For tested units, quote terms can include 7-day DOA support unless otherwise stated.
Independent sourcing disclaimer
We are not an authorized distributor, reseller, or representative of Siemens, Mitsubishi, Omron, or other manufacturers listed on this site. All product names, trademarks, brands, and logos are the property of their respective owners. Products may be used, refurbished, surplus, or sourced from the secondary market unless otherwise stated.
Prices and stock can change. Submit quantity, required condition, and destination for a current quote.
0 to 10.24 VDC across four single-ended channels
Maximum update rate is 0.3 ms
Outputs can hold last state or default to 0 V via jumper, if user power remains
Recommended +18 to +30 VDC user-side supply
Use shielded twisted pair for all analog channels